How to Wire a Multi-tap Transformer

This week, we go over how to wire our transformers!

E2021 Tech Tuesday Blog Banner 2019

Occasionally we get calls from customers asking which wires to connect to our multi-tap transformers. This is understandable, considering all the wires involved. Luckily, the solution is an easy one to remember once you know it.

A large part of being able to figure this out is knowing how your 3-phase incoming power is set up. Typically, they’re in either a delta or wye configuration.

Delta Configuration

Multi-Tap Transformer Delta Configuration Wiring Diagram

WYE Configuration

Multi-Tap Transformer WYE Configuration Wiring Diagram

An easy way to remember this is that the delta configuration looks like a delta symbol, and the wye configuration looks like the letter “Y”. The wye configuration also looks a bit like a flux capacitor from Back to the Future if that helps. Please note that not every delta or wye set up will have these voltages, these are just two examples. The main point to get from this is that your incoming power typically has three phases and one neutral. This allows each configuration to provide two to three different voltages. Usually, between neutral and a phase is a smaller voltage, and between two different phases is a larger voltage. Knowing which voltage is between which two wires is key when installing one of our multi-tap transformers.

Measuring Wire Voltage

If you don’t know which wire is which, you can always measure it using your multimeter. Once you know which two wires have the voltage for the tap you want, simply connect one power wire to the wire on our transformer with the voltage tap you want, and the other power wire to the wire on our transformer labeled “Comm”. Then separately insulate each of the unused wires. It’s that easy!

For the sake of clarity let’s do some examples. Take a look at the wiring diagram for our TR50VA015:

TR50VA015 Wiring Diagram

Let’s say you want to connect the above delta configuration to our TR50VA015. If you wanted to connect 120 Vac to the primary, you would connect your neutral (WHITE) to the transformer Comm (Blk). Then you would either connect phase A or C (BLACK or BLUE) to the 120 Vac tap on the transformer (Wht). If you wanted to use 240 Vac on the primary, you would take any two of the three phases and connect them to the orange and black wires on the transformer. It doesn’t matter which phase goes to which wire.

For the above wye configuration, you would connect your neutral (GRAY) and any phase to the black and brown wires on the transformer for a 277 Vac primary. Similarly, any two phases on the wye configuration should be connected to the gray and black wires on the transformer for a 480 Vac primary.

Hopefully this clarifies how to wire one of our transformers. As always, if you’re still confused, feel free to contact us!